Açıklama
Application
Locations under mechanical stress , underground , in power and switching stations , industrial plants
Cable Design
| Conductor | Electrolytic Copper Wire, Class 1/2, EN 60228, IEC 60228, VDE 0295 |
| Insulation | XLPE Compaund |
| Insulation Colour | Determined by Mutual Agreement |
| Stranding | Cores Twisted in Layers |
| İnner Sheath | PVC Filler Compound |
| Armour | Galvanized Round Steel Wire |
| Outer Sheath | PVC Compaund (UV and Oil Resistance) |
| Outer Sheath Color | Determined by Mutual Agreement |
| Operatıng Voltage [kV] | 0,6/1 kV |
| Test Voltage [kV] | 3.5 kV |
| Bending Radius [mm] | 12xD |
| Max. Operating Temperature | 90ºC |
Tests
| Flame Retardant Test | IEC 60332-1-2;VDE 0482-332-1-2;EN 60332-1-2 |
Technical Characterstıces
|
Products Code |
Cross Section |
Conductor Resistance at 20°C |
Overall Diameter |
Delivery length |
Approx. Cable Weıght |
Current Carrying Capacity | |
| In Ground at 20°C | In Air at 30°C | ||||||
| — | mm² | Ωxkm | mm | m | kg/km | A | A |
| 32.22.34.01.20.Ç.1 | 1×500 ** | 0,0605 | 42,7 | 1000 | 2650 | 601 | 754 |
| 32.22.34.05.09.Ç.1 | 5×16 | 1,91 | 25,6 | 1000 | 1290 | — | — |
| 32.22.34.05.15.Ç.1 | 5×120 | 0,25 | 57,3 | 500 | 5895 | 268 | 273 |